Skip to content
Specialist component specification

Pultruded CFRP strengthening strips: a steel plate's tension at a tenth of the weight, bonded on by hand

A pultruded carbon strip bonded to the tension face of a concrete beam, slab or wall adds flexural capacity without adding depth, weight or a crane: 150–170 GPa class stiffness and 2,500–3,000 MPa strength in a 1.2–1.4 mm laminate that two people carry and press into fresh epoxy. F1 Composite pultrudes strips to the width, thickness and cut length the strengthening system and the engineer of record specify, with the laminate data, bonding face and batch records they ask for. The system, the adhesive and the design remain theirs.

FIG. 1 A strip going onto a beamPhoto · see credits
Installer on a scaffold pressing a 5 mm CFRP strip onto the prepared soffit of a concrete beam
A 5 mm pultruded CFRP strip being pressed onto the prepared soffit of a beam, 2026. The concrete was ground and primed first; the strip goes on by hand, from a scaffold, on a live structure.
EB strips
50–120 × 1.2–1.4 mm class
Stiffness along the fibers
150–170 GPa class
Weight, same tension
≈ 1/10 of a steel plate
Supply
Cut lengths or coils, to the schedule

Last updated

What a bonded carbon strip does that a steel plate cannot, and what it will not do

Externally bonded strengthening used to mean a steel plate, bolted and glued to the soffit, rusting where nobody could see it. A pultruded carbon strip does the same job at a tenth of the weight, without corrosion, from a scaffold with hand tools. The numbers are class values for strengthening-grade strips; the strip's qualification report is what the designer uses.
FIG. 2 The stripPhoto · see credits
A 1.4 mm thick pultruded CFRP strengthening strip held in a hand against white paper
A 1.4 mm pultruded CFRP strip, the standard thickness of externally bonded strengthening systems: 50–120 mm wide, cut to the member, light enough to carry rolled up.
FIG. 3 Stiffness per unit mass
Bar chart of stiffness per unit mass: unidirectional pultruded carbon fiber about 87, aluminium 26, steel 25, pultruded fiberglass E23 about 12 GPa per gram per cubic centimetre
Unidirectional pultruded carbon against aluminium, steel and E23 fiberglass. Same mass, about 3.4 times the stiffness of the metals along the fibers; a strengthening-grade strip sits at the top of the carbon range.
FIG. 4 On the slabPhoto · see credits
Carbon fiber strips bonded in a grid onto the prepared top surface of a concrete floor slab
CFRP strips bonded to a prepared slab surface, laid along the span and anchored across it. The concrete was ground and cleaned first; the bond line is the design.

Reason 1

A steel plate's tension at a tenth of the weight

A 50 × 1.4 mm strip carries about the ultimate tension of a 50 × 8 mm mild-steel plate. Two people carry a 10 m length; it goes up by hand from a scaffold and is pressed into fresh epoxy.

Strengthening-grade strips: 150–170 GPa modulus, 2,500–3,000 MPa tensile strength at 65–70% fiber volume. 70 mm² × 2,800 MPa ≈ 400 mm² × 490 MPa.

Reason 2

No added depth, no lost headroom

The strip adds 1.4 mm plus a 1–3 mm bond line to the soffit. The floor-to-ceiling height, the services and the finishes stay where they are; a steel plate or a concrete overlay would not allow that.

EB strips sit on the surface; NSM strips sit inside the existing cover in a 15–25 mm groove and add nothing at all.

Reason 3

It never rusts at the bond line

A bonded steel plate corrodes behind the adhesive where no inspection can see it. A carbon strip does not corrode, does not fatigue under traffic cycles, and keeps its stiffness for the life of the repair.

No electrochemical corrosion; high fatigue limit in tension along the fibers; creep rupture is checked on the adhesive, not the carbon.

Reason 4

Installed overnight, on a live building

Grind, prime, bond, cure: no welding, no bolting into tensioned bars, no crane, no shutdown. A strengthening crew can do a floor of beams between one working day and the next.

Hand tools and an epoxy that cures in hours; the structure keeps carrying its dead load throughout.

The bond is the capacity

The strip almost never breaks. The joint fails by peeling at a square-cut end, delaminating off weak or dusty concrete, or softening above the adhesive's glass transition. Substrate pull-off strength, surface preparation, anchorage length and end detail are the design.

Fire and impact are not the strip's job

An EB strip is exposed. Fire rating comes from the existing member and any applied protection, and the strengthened capacity is usually limited so the member survives without the strip. NSM strips are inside the cover and better protected.

Strain is limited, so is the gain

Codes cap the strip strain to stop debonding well before rupture, and cap the total strengthening so the unstrengthened member still carries a set share of the load. A strip typically adds tens of percent of flexural capacity, not multiples.

It is one part of an assessed kit

The adhesive, the primer, the strip and the method are assessed together. A strip with the right numbers is still only a candidate until the system supplier and the engineer of record accept it; F1 supplies the strip to their specification, not the kit.

Externally bonded, near-surface-mounted, or a steel plate

The same beam can be strengthened three ways. The strip's numbers are the same in two of them; where it sits decides the bond, the protection and the site work.
FIG. 5 Three ways to add tension to a beam
Three beam cross-sections strengthened with an externally bonded CFRP strip, a near-surface-mounted strip in a sawn groove, and a bonded steel plate, with typical sizes and the governing failure for each
An externally bonded strip on the soffit, a near-surface-mounted strip or bar in a sawn groove, and the bonded steel plate CFRP replaced. Sizes are the ranges strengthening systems publish; the design is to ACI 440.2R / 440.13, fib Bulletin 90 or TR55 by the engineer of record.

Externally bonded (EB)

The default. No groove, fastest to install, the whole strip face is bond area. Exposed, so fire and impact are handled by the member and the design limits, and the ends need a taper, a clamp or a U-wrap to stop peel.

Near-surface-mounted (NSM)

A narrow strip or a bar in a sawn groove, bonded on three sides, inside the cover: two to three times the bond of an EB strip, protected from traffic and fire, and the only option on a slab top that will be walked on. Needs 15–25 mm of sound concrete below the existing bars.

Wet lay-up fabric instead

Dry unidirectional fabric laid on site with epoxy follows a curved surface, wraps a column or forms a U-jacket. For a flat tension face a pultruded strip is the same fiber at a higher, more uniform fiber content with none of the site lay-up risk.

The bond is the design

A strip adds capacity only through its bond line. The strip almost never fails; the adhesive peels off a square-cut end, delaminates from weak concrete or softens above its glass transition. The drawing, the surface preparation and the end detail are where the engineering goes.
FIG. 6 A strip bonded to a member
Section schematic of a pultruded carbon strip bonded to a concrete substrate showing the adhesive bond line, anchorage length, tapered ends and end-peel arrow, with the seven items the joint needs on the drawing
Fibers along the member, prepared face down, a 1–3 mm thixotropic epoxy bond line, anchorage past the point where the strip is needed, tapered or clamped ends. The seven items the joint needs on the drawing are listed on the figure.
FIG. 7 The bonding facePhoto · see credits
Edge of a 5 mm pultruded carbon plate with the frayed peel-ply fabric still attached along both faces
A 5 mm pultruded carbon plate with its peel ply still on: the sacrificial fabric is pulled off on site to leave a clean, textured bonding face. Which face is prepared is specified with the strip.

Who owns what

  • · Engineer of record: the capacity to add, strain limits, anchorage, the code
  • · System supplier: the adhesive, primer, method statement and the assessed kit
  • · Installer: substrate preparation, pull-off tests, bond-line thickness, records
  • · F1 Composite: the strip to the specified width, thickness, face and length, with laminate data and batch records

Where a strengthening strip is specified

Four cases account for most strip orders. The photographs show the element, not an F1 project; the strips in them were supplied by the strengthening contractors who took the pictures.
Installer on a scaffold pressing a 5 mm CFRP strip onto the prepared soffit of a concrete beam

A 5 mm pultruded CFRP strip being pressed onto the prepared soffit of a beam, 2026. The concrete was ground and primed first; the strip goes on by hand, from a scaffold, on a live structure.

Beams and slabs under a new load

A change of use, heavier equipment, a mezzanine, a new partition: the member needs more flexural capacity and the floor cannot get thicker. Strips on the tension face are the standard answer.

Typical
50–100 mm × 1.2–1.4 mm strips along the span, one to three per beam, lengths to the member
What to send
The member and its drawings, the existing capacity, the new load case and the design code the engineer of record works to.
Grid of bonded black carbon fiber strips on a concrete floor slab around a newly cut square opening

Pultruded CFRP strips bonded around a new opening in a concrete slab: the construction use of pultruded carbon, where a thin strip or rod adds tensile capacity without adding weight or depth.

New openings in slabs and walls

Cutting a stair or a service opening removes reinforcement. Strips bonded around the opening restore the load path across it without a steel frame.

Typical
50–80 mm strips along both edges of the opening, lapped past the corners
What to send
The opening position and size, the slab reinforcement, and whether the strips can run on the top face, the soffit or both.
Carbon fiber strips bonded in a grid onto the prepared top surface of a concrete floor slab

CFRP strips bonded to a prepared slab surface, laid along the span and anchored across it. The concrete was ground and cleaned first; the bond line is the design.

Corroded or missing reinforcement

Where chlorides or carbonation have taken bars out of service, strips replace the lost tensile steel on the face after the concrete is repaired, without breaking out the member.

Typical
Strips sized to the lost steel area; concrete repair mortar first, then the bond
What to send
The condition survey, the repaired substrate's pull-off strength and the exposure the repair must survive.
Bundle of ribbed CFRP bars laid on cardboard with a handwritten cut list beside them

Ø6 and Ø10 CFRP bars cut to a schedule, the near-surface-mounted alternative to a strip: the bar sits in a sawn groove, bonded on three sides and protected by the cover.

Near-surface-mounted strips and bars

Where the surface will be trafficked, exposed to fire or impact, or where the member is a slab top rather than a soffit, the strip or a bar goes into a sawn groove and is bonded on three sides, inside the cover.

Typical
10–20 × 2–3 mm strips or Ø6–Ø10 bars in 15–25 mm grooves; 2–3 times the bond of an EB strip
What to send
Cover depth and bar positions from a scan, the groove layout, and the adhesive the system specifies for grooves.

The application guide, with the intervention logic, reinforcement position, installation planning and acceptance records, is on the CFRP concrete strengthening page. Wider flat laminates for spar caps and stiffeners are on the pultruded carbon fiber plates page.

The strip itself: what F1 pultrudes and how it ships

A strengthening strip is the simplest carbon profile: unidirectional tow, an epoxy or vinyl ester matrix, pulled flat through a die at the highest fiber content pultrusion reaches, with the bonding face finished as the system specifies.
FIG. 8 Pultruded strip, not laid-up fabricPhoto · see credits
Roll of dry unidirectional carbon fiber fabric in plastic wrap on a cardboard core
Dry unidirectional carbon fabric, the other half of the strengthening market: wet-laid on site with epoxy for wraps, U-jackets and curved surfaces. A pultruded strip is the same fiber already cured flat at a higher fiber content.
FIG. 9 Coiled for transportPhoto · see credits
Thin pultruded CFRP strips coiled into a large ring and strapped for transport in a warehouse
Strips coiled for transport: a 1.2–1.4 mm strip bends to a metre or so of diameter without damage, so long lengths ship in a crate instead of on a flatbed.

On the order

  • · Width and thickness to the schedule: 50–120 × 1.2–1.4 mm class for EB, 10–20 × 2–3 mm for NSM; other sections to drawing
  • · Bonding face: peel ply, abraded or as pultruded, on the face you name
  • · Laminate data in the fiber direction to ISO 10406-3 or ASTM D7205, with the basis stated
  • · Cut lengths labelled by mark, or coils for long strips; packed flat or coiled
  • · Batch records linking each strip to its laminate and inspection evidence

Class values on this page are published ranges for strengthening-grade unidirectional carbon strips (ACI 440.2R, supplier datasheets); they are not an F1 datasheet, stock list or kit approval. The sections below say how to turn them into a purchase specification.

Put the functional geometry on the purchase drawing

Give each strip a part number linked to width, thickness, length and the permitted tolerances. Define how those dimensions are measured and whether the requirement applies before or after any surface treatment. Include straightness, edge condition and end-cut requirements where they affect fitting or bonding. A supplier needs the actual section rather than an approximate area calculated from a rounded catalog dimension.

State whether delivery is in individual lengths or another agreed format, and establish transport and handling requirements for that format. The reinforcement drawing should identify orientation and installed position without relying on removable packaging. If lengths will be cut on site, assign the cutting procedure, identification transfer and final inspection to a named party. Material availability and packaging geometry are quotation items, not assumed stock commitments.

ReferencesEAD 160086-01-0301: CFRP strengthening kitsSika CarboDur System: application method statement

Request material data on an agreed basis

Specify the properties needed by the designer, including longitudinal stiffness and tensile behavior, together with the applicable test method and acceptance basis. Distinguish typical development data from declared or statistically established design inputs. The source of a value, specimen orientation, conditioning and representative production construction should be identifiable. An isolated high test result is not a procurement specification. ISO 10406-3:2019 gives test methods for pultruded CFRP strips used as externally bonded reinforcement; on European projects the bonding adhesive is normally declared under EN 1504-4.

Define the permitted reinforcement and matrix system and how changes are controlled. Where thermal or environmental performance matters, agree on the evidence and conditioning relevant to the project. A carbon strip's resin temperature data should not be presented as the service limit of an adhesive joint. The purchaser should state which characteristics are mandatory for tender review and which need to be established during development.

ReferencesACI PRC-440.2-23: FRP strengthening guideISO 10406-3:2019: test methods for CFRP strips

Make the bonding face a controlled interface

Identify the intended bonding face, its surface preparation, protection during transport and compatibility requirements. Surface texture alone does not demonstrate a qualified adhesive interface. The system owner should determine the acceptance evidence for the actual strip, adhesive, concrete and any repair layer. Preserve the identity of the proposed materials during sample evaluation so the production component can be compared with what was accepted.

Define whether the order covers only strips or components of an assessed kit. Include exclusions and interfaces in the quotation, such as adhesive supply, site preparation and installation supervision. If an existing system approval is a project requirement, check its exact products and allowed variations before purchasing an alternative strip. A reference to an assessment document is not evidence that the offered material belongs to an assessed system.

ReferencesEAD 160086-01-0301: CFRP strengthening kits

Agree on sample release, inspection and batch records

Set a qualification stage before serial delivery: approve the drawing and material proposal, identify representative samples and agree on test acceptance. The inspection plan can cover dimensions, visual condition, bonding-face protection and the specified material tests. Record the criteria for disposition of damaged edges, surface contamination or mismarked pieces. Do not leave rework decisions to a generic visual-quality statement.

Request a delivery record that connects the part number and batch to the relevant material and inspection evidence. Specify how identification survives unpacking, cutting and installation. Agree on protective packaging, handling instructions, storage conditions and an incoming-inspection period. These controls support a traceable component purchase; final acceptance of the strengthened member also requires the system designer's and installer's project records.

ReferencesACI PRC-440.2-23: FRP strengthening guide

Standards, regulations and acceptance evidence

The project authority determines the governing jurisdiction and adopted edition. The scope of each reference matters: a material test method, a design guide and an assessment route each cover a different part of the strengthening system.

Guidance · United States origin; use where accepted by the project designer and authority

ACI PRC-440.2-23

Engineering, construction and inspection guidance for FRP used in externally bonded or near-surface-mounted concrete strengthening.

Application boundary: A guide, not a product certificate or an automatic legal approval. The project design must define enforceable requirements. It is distinct from standards for internal GFRP reinforcing bars.

ReferencesACI PRC-440.2-23: FRP strengthening guide

Standard · Projects adopting this code through the governing code, authority or contract

ACI CODE-440.13-24

Minimum requirements for strengthening existing concrete with the unidirectional externally bonded and near-surface-mounted FRP systems permitted by its Chapter 4.

Application boundary: Publication does not make it law everywhere or certify a product. Masonry is excluded. Seismic strengthening of seismic-force-resisting members in Seismic Design Categories B–F is outside its scope; the designer must establish the applicable route.

ReferencesACI CODE-440.13-24: FRP concrete-strengthening codeACI CODE-440.13-24: official preview and scope

Assessment route · European technical assessment route for construction products

EAD 160086-01-0301

Assessment of concrete-strengthening kits comprising unidirectional carbon/epoxy strips and an epoxy structural bonding agent, for externally bonded or near-surface-mounted use.

Application boundary: Strip width and thickness must be prefabricated in the plant; site cutting to width is excluded. The stated intended use excludes seismic retrofitting and prevention. An EAD is not an ETA: verify the actual kit and assessment scope. EOTA lists the earlier -00 version as superseded.

ReferencesEAD 160086-01-0301: CFRP strengthening kitsEOTA: European Assessment Document register

Public source scopes were reviewed on . These references do not establish that any F1 product is approved, listed or part of an assessed kit.

Pultruded CFRP strengthening strips: practical questions

How much capacity does a strip add?

Typically tens of percent of flexural capacity, not multiples. Codes cap the strip strain to stop debonding well before rupture and cap the total strengthening so the unstrengthened member still carries a set share of the load (ACI 440.2R limits the strengthened member to a fraction of the new load without the strip). The engineer of record sets the number; the strip's modulus and the bond decide whether it is reachable.

Externally bonded or near-surface-mounted?

EB on a soffit or a wall face where nothing touches it: fastest, cheapest, the whole face is bond area. NSM where the surface is trafficked, exposed to fire or impact, or is a slab top: a narrow strip or a bar in a sawn groove, bonded on three sides inside the cover, with two to three times the bond of an EB strip. NSM needs 15–25 mm of sound concrete below the existing bars.

Why a pultruded strip rather than wet lay-up fabric?

For a flat tension face the strip is the same carbon at a higher and more uniform fiber content, already cured, with a controlled thickness and bonding face; the site crew bonds a finished laminate instead of impregnating fabric overhead. Fabric wins on curved surfaces, column wraps and U-jackets, where a strip cannot follow the shape.

Are these catalog stock strips?

This is a specification and qualification route. Dimensions, availability, minimum order and evidence requirements must be reviewed before a product offer is confirmed.

Is adhesive included?

Only if expressly included in an agreed scope with compatibility and system evidence. A strip-only quotation does not establish an accepted strengthening kit.

Can wind-blade laminate data be used for this strip?

Not automatically. The offered construction, bonding interface, property basis and intended strengthening use need project qualification.

Can a wide plate be slit on site under EAD 160086-01-0301?

No. Its scope excludes strips cut on site to the required width. Specify the factory-produced width and thickness. Cutting to length is a separate installation operation that must follow the selected kit's instructions and the project specification.

Technical sources and further reading

Industry sources establish where the strip is used. Authority sources define the published scope of standards and assessment routes. The design responsibility stays with the engineer of record and the system supplier.
  1. Standard or public authority

    ISO 10406-3:2019: test methods for CFRP strips

    Test methods for unidirectional pultruded CFRP strips used as externally bonded reinforcement on concrete. Results describe the strip, not a bonded strengthening system.

  2. Industry application evidence

    Epsilon Composite: pultruded carbon flat laminates

    Evidence of a commercial carbon/epoxy strip application in civil engineering; proprietary products and performance are not F1 specifications.

  3. Standard or public authority

    ACI PRC-440.2-23: FRP strengthening guide

    Publisher's scope for engineering, construction and inspection of externally bonded and near-surface-mounted FRP strengthening systems. The full guide is not reproduced.

  4. Standard or public authority

    ACI CODE-440.13-24: FRP concrete-strengthening code

    Official publisher listing for the 2024 design code. Its publication does not establish adoption by a particular jurisdiction or project.

  5. Standard or public authority

    ACI CODE-440.13-24: official preview and scope

    The public preview includes the preface and Sections 1.1–1.2, establishing concrete-only, permitted-system and seismic limits. It does not provide the full design provisions.

  6. Standard or public authority

    EOTA: European Assessment Document register

    Lists EAD 160086-01-0301 and identifies the earlier 160086-00-0301 as superseded.

  7. Standard or public authority

    EAD 160086-01-0301: CFRP strengthening kits

    Sections 1.1–1.2 define the carbon/epoxy strip and bonding-agent kit, manufacturing dimensions and intended-use limits. This assessment document is not an approval of F1 products.

  8. Industry application evidence

    Sika CarboDur System: application method statement

    A manufacturer's system-specific example of installation and inspection controls. Its adhesive, dimensions, environmental limits and cure times must not be transferred to another system.

Prepare a strip qualification brief

Send the strip schedule, the placement, the adhesive system and the evidence the designer needs so we can confirm the section, the laminate data, the bonding face and the supply scope. We reply within one business day; a formal quotation follows once the specification and delivery are reviewed.

01 · Part-numbered strip schedule: width, thickness, length, quantity, tolerances and measurement conditions.
02 · Material system, required property basis, test methods, conditioning and acceptance criteria.
03 · Bonding-face definition, protection and the intended adhesive/system qualification evidence.
04 · Externally bonded (EB) or near-surface-mounted (NSM) use, drawing revision and responsible designer or kit supplier.
05 · Prototype and serial release requirements, inspection records, marking and traceability.
06 · Delivery format, handling constraints, destination, storage period and installation program.
Get a quoteWhatsApp