Fiberglass catwalk grating: key facts
Fiberglass catwalk grating is molded or pultruded FRP grating laid on stringers as the deck of a maintenance walkway. Most catwalks use a 38 × 38 mm molded mesh 25 to 38 mm deep, or a pultruded I-bar panel where the supports are further apart, fixed with stainless steel clips.
- What it is
- FRP grating used as the deck of a narrow elevated walkway for maintenance and service access.
- Molded rows
- 38 × 38 mm square mesh, 25, 30, 38 mm deep, 12.3 to 19.5 kg/m² nominal.
- Pultruded rows
- I-bar series in 25, 30 and 38 mm depths with 40%, 50% or 60% open area.
- Catwalk load
- ASCE 7-22: 40 psf (1.92 kPa) with a 300 lb (1.33 kN) concentrated load for maintenance catwalks.
- Clear width
- EN ISO 14122-2 and AS 1657: at least 600 mm.
- Fixing
- 316 stainless steel clips, at least four hold-downs per panel as a starting layout.
Loads and widths a catwalk is designed to
| Rule | Applies to | Load |
|---|---|---|
| ASCE 7-22 Table 4.3-1 (US) | Catwalks for maintenance and service access | 40 psf (1.92 kPa) and 300 lb (1.33 kN) concentrated |
| ASCE 7-22 Table 4.3-1 (US) | Walkways and elevated platforms other than exitways | 60 psf (2.87 kPa) |
| OSHA 29 CFR 1910.22(b) (US) | Every walking-working surface | Its maximum intended load; no fixed value |
| EN ISO 14122-2:2016 (EU/UK) | Working platforms and walkways | 2 kN/m² on the structure; 1.5 kN on 200 × 200 mm on the flooring; deflection no more than span/200 and 4 mm step to the adjacent unloaded panel |
| AS/NZS 1170.1 and AS 1657:2018 (AU/NZ) | Walkways and platforms | Take the values for the occupancy from the standard; AS 1657 walkways are at least 600 mm wide with 2,000 mm headroom |
A catwalk used only for maintenance carries a lighter floor load than a general platform, but the 300 lb concentrated load and the deflection limit usually decide the grating depth and the support spacing.
Edge protection follows a separate rule. OSHA 1910.28 requires fall protection where a walking-working surface has an unprotected edge 4 ft (1.2 m) or more above a lower level, and 1910.29 sets the guardrail top edge at 42 in ± 3 in with a toeboard at least 3.5 in high where objects could fall on people below.
Check the geometry of a layout in the access geometry checker.
Grating rows used for catwalks
| Type | Mesh or series | Depth | Open area | Weight | Use on a catwalk |
|---|---|---|---|---|---|
| Molded | 38 × 38 mm square mesh | 25 | 68% | 12.3 | Spans both ways; cut-outs can be made on site without losing the panel |
| Molded | 38 × 38 mm square mesh | 30 | 68% | 14.6 | Spans both ways; cut-outs can be made on site without losing the panel |
| Molded | 38 × 38 mm square mesh | 38 | 68% | 19.5 | Spans both ways; cut-outs can be made on site without losing the panel |
| Pultruded | I-4010 I-bar | 25 | 40% | 17.1 | Bearing bars at 25.4 mm centers; spans one way, across the stringers |
| Pultruded | I-5010 I-bar | 25 | 50% | 14.2 | Bearing bars at 30.0 mm centers; spans one way, across the stringers |
| Pultruded | I-6010 I-bar | 25 | 60% | 11.2 | Bearing bars at 38.1 mm centers; spans one way, across the stringers |
| Pultruded | I-40125 I-bar | 30 | 40% | 19.8 | Bearing bars at 25.4 mm centers; spans one way, across the stringers |
| Pultruded | I-50125 I-bar | 30 | 50% | 17.4 | Bearing bars at 30.5 mm centers; spans one way, across the stringers |
| Pultruded | I-60125 I-bar | 30 | 60% | 13.5 | Bearing bars at 37.1 mm centers; spans one way, across the stringers |
| Pultruded | I-4015 I-bar | 38 | 40% | 22.0 | Bearing bars at 25.4 mm centers; spans one way, across the stringers |
| Pultruded | I-5015 I-bar | 38 | 50% | 19.1 | Bearing bars at 30.5 mm centers; spans one way, across the stringers |
| Pultruded | I-6015 I-bar | 38 | 60% | 16.1 | Bearing bars at 37.1 mm centers; spans one way, across the stringers |


Full tables and panel sizes: molded FRP grating and pultruded FRP grating. All grating families: fiberglass grating. Choosing between the two: molded vs pultruded grating.
Supports, fixing and edge protection
Stringers
Two or more stringers run the length of the catwalk and set the grating span. They are usually pultruded channel, I-beam or fiberglass square tube, or the existing steel.
Clips
Hold-downs go at every support line: at least four per panel and no more than 1,200 mm apart along a support as a starting layout. See fiberglass grating clips.
Guardrail and toe board
Posts, rails and toe boards come from the fiberglass handrail systems page and bolt to the stringers, not to the grating.
Access
Stairs, ladders and crossovers that reach the catwalk are covered under FRP access platforms and stairs.
Lay pultruded panels with the bearing bars across the stringers. Support every cut edge and every panel end, and re-check the clip layout after cut-outs for pipes or columns. A gritted top is the usual surface for a catwalk that gets wet or oily.
Catwalk grating questions
What is fiberglass catwalk grating?
It is molded or pultruded FRP grating used as the walking surface of a catwalk: a narrow elevated walkway for maintenance and service access along process lines, tank tops, roofs and pipe racks. The panels sit on stringers or existing steel and are held down with clips.
What load does catwalk grating have to carry?
The load comes from the rule that governs the structure. ASCE 7-22 Table 4.3-1 and IBC Table 1607.1 list 40 psf with a 300 lb concentrated load for catwalks used for maintenance and service access, and 60 psf for walkways and elevated platforms other than exitways. EN ISO 14122-2 uses 2 kN/m² on the structure and 1.5 kN on a 200 × 200 mm area of the flooring.
How wide should a catwalk be?
EN ISO 14122-2 asks for a clear width of at least 600 mm, recommends 800 mm, and 1,000 mm where several people pass. AS 1657 also sets 600 mm as the minimum. Guardrail posts and toe boards take up width, so set the grating panel wider than the clear walking width.
Molded or pultruded grating for a catwalk?
Molded grating carries load in both directions, so it suits catwalks with cut-outs, angled ends and irregular supports. Pultruded grating has more glass along the bearing bars and spans further one way, which reduces the number of supports on a long straight run. Both are held with the same family of clips.
How is catwalk grating fixed down?
With stainless steel hold-down clips at the supports. As a starting layout, use at least 4 hold-downs per panel and at least 2 on each support line, with a bearing length of 38 mm (1.5 in) or more. The approved layout drawing sets the final quantity.
Do you supply the catwalk structure as well as the grating?
Yes. Stringers and cross members come from the pultruded channel, I-beam and square tube catalog, guardrails from the handrail system, and stairs from the stair tread range. Send the layout and loads; the structure is designed for the project by the responsible engineer.
Quote catwalk grating
Send the catwalk layout with support spacing, the load rule and the exposure. We return the panel series and depth, a panel layout and the clip count. We reply within one business day; a formal quotation follows once the specification and delivery are reviewed.
- Layout
- Length, clear width, support positions and spacing, cut-outs and changes of direction.
- Load rule
- ASCE 7, EN ISO 14122, AS 1657 or the project value, with the deflection limit.
- Exposure
- Chemicals, temperature, outdoor UV, and any fire or conductivity requirement.
- Scope
- Grating only, or grating with stringers, handrail, toe board, stairs and clips.